
Switchgear components work together to switch, protect, control and isolate electrical circuits. Common parts include circuit breakers, protection relays or trip units, busbars, disconnectors, fuses, instrument transformers, control circuits and enclosures.
The exact components depend on the voltage, circuit function and assembly design. Not every switchgear panel contains every device listed in this guide.
For an introduction to the complete assembly, read what switchgear is and where it is used.
| Component | Main function |
|---|---|
| Circuit breaker | Makes, carries and interrupts current within its specified ratings |
| Protection relay or trip unit | Detects defined abnormal conditions and initiates protection |
| Busbar | Carries and distributes current between connected circuits |
| Disconnector | Provides a specified isolation function |
| Earthing switch | Connects designated conductors to earth |
| Current transformer or sensor | Provides current information for protection and measurement |
| Voltage transformer or sensor | Provides voltage information for protection and measurement |
| Fuse | Interrupts overcurrent according to its characteristics |
| Contactor | Performs frequent load switching within its rated duties |
| Surge-protection device or arrester | Limits specified transient overvoltages |
| Control circuits and interlocks | Manage commands, indications and permitted operations |
| Enclosure and internal barriers | Provide specified protection, separation and access arrangements |
These devices must be coordinated as part of an engineered assembly. Selecting suitable individual parts does not, by itself, establish that the complete switchgear meets its requirements.
A circuit breaker switches a circuit and interrupts normal or fault current within its rated capabilities.
Depending on the application, switchgear may use air circuit breakers, moulded-case circuit breakers, vacuum circuit breakers or other technologies.
Selection must address operating voltage, continuous current, interruption duties and compatibility with the assembly. A breaker’s normal current rating alone does not establish whether it can interrupt the available fault current.
A protection relay evaluates electrical measurements and issues a trip command when its configured criteria are met. Separate relays are common in many MV protection arrangements.
A trip unit performs protection functions associated with a circuit breaker. LV breakers may use thermal-magnetic or electronic trip units, so a separate protection relay is not always required.
Available functions depend on the device. They may include overcurrent, earth-fault, voltage or other protection.
The protective device identifies the condition requiring action; the circuit breaker physically interrupts the current.
A busbar carries current between incoming connections, outgoing circuits and other assembly sections.
Busbar design must account for:
The main power busbars and protective earthing conductors perform different functions. Their arrangements must follow the assembly design.
A disconnector provides a defined isolation function. It should not be assumed capable of interrupting load or fault current unless specifically rated for that duty.
A switch-disconnector combines specified switching and isolation functions.
An earthing switch connects designated conductors to earth. Its operation must follow the equipment instructions and approved site procedures.
Interlocks can restrict certain operations, but they do not replace verification of isolation or other required precautions.
Current transformers, voltage transformers and suitable sensors provide signals for protection, metering and control.
| Device | Information provided |
|---|---|
| Current transformer or current sensor | Circuit current |
| Voltage transformer or voltage sensor | Circuit voltage |
Selection depends on the measurement or protection duty, required accuracy, insulation and connected equipment.
Not every protection function needs both current and voltage inputs. The required devices follow the protection scheme.
Conventional CT secondary circuits can develop hazardous voltages if opened while primary current flows. Work on these circuits requires qualified personnel and approved procedures.
A fuse interrupts overcurrent by melting its element. It must be selected for the required voltage, breaking capacity, operating characteristics and coordination.
A contactor is primarily intended for repeated load switching, such as controlling motors. It normally requires coordinated short-circuit protection and, where applicable, overload protection.
A contactor should not be treated as a substitute for a protective circuit breaker.
Control circuits connect operating commands, protection outputs, status indications and alarms.
They may include:
Interlocks restrict operations according to the design. They may prevent incompatible source connections, inappropriate breaker movement or access to certain compartments.
The functions provided must be confirmed from the equipment documentation.
LV and MV assemblies perform related functions, but their component arrangements differ.
| Function | Typical LV arrangement | Typical MV arrangement |
|---|---|---|
| Current interruption | Air or moulded-case breakers, fuses and other rated devices | Vacuum or other rated breakers; switch-fuse arrangements where specified |
| Fault detection | Integral trip units, fuses or separate protection devices | Protection relays with instrument transformers or sensors in many arrangements |
| Measurement | Meters, current transformers and suitable sensing arrangements | Current/voltage transformers or sensors selected for the scheme |
| Isolation | Suitable isolating devices or breaker arrangements | Disconnectors, switch-disconnectors or withdrawable arrangements, depending on design |
| Earthing | Protective earthing conductors and terminals | Protective earthing plus designated earthing switches where provided |
| Insulation | Clearances and insulation appropriate to LV duties | Insulation systems selected for the specified MV ratings |
These are typical examples, not mandatory inventories. LV systems can use separate relays, and some MV circuits use fuse-based protection.
Compare LV, MV and HV switchgear for their roles within the network.
The enclosure and internal barriers provide the specified protection against access to hazardous parts and environmental exposure. They also support components, cable connections and maintenance access.
An IP rating addresses particular access and ingress-protection characteristics. It does not establish internal-arc performance or explosion protection.
Likewise, a metal enclosure does not automatically make equipment metal-clad or arc-resistant.
Read about switchgear types and construction for further distinctions.
In a relay-controlled arrangement, measurements reach the relay, the relay evaluates the condition and a trip command operates the breaker.
In other arrangements, an integral trip unit or fuse provides the protective response.
Protection coordination aims to disconnect the affected section while limiting unnecessary interruption elsewhere. The outcome depends on the network and protection design.
Read how switchgear works for a detailed explanation.
Review components within the complete assembly specification:
Replacing a component with one that has a similar current rating does not establish compatibility. Confirm the manufacturer’s requirements and any effect on assembly performance.
For Saudi projects, review the applicable requirements through our switchgear standards and compliance guide.
No. Protection may be provided by an integral breaker trip unit or fuses. Separate relays are used where the scheme requires them.
Do not assume so. Dimensions, interfaces, ratings, controls and assembly verification may differ.
Compatible relays, meters and controllers can provide supported measurements and status information. Communication functions and protocols must be specified.
Requirements depend on the assembly. Breakers, mechanisms, connections, insulation, control supplies and protection equipment may need inspection or testing according to manufacturer instructions and operating conditions.
Request a component schedule showing exact device references, ratings and protection functions. Check it against the drawings, studies and assembly requirements.
Our guide to choosing switchgear suppliers explains how to compare technical submissions.